S2UI28

Price:
$450.00 CAD

Wall-Mounted User Interface Terminal


Overview

The S2UI28 is a wall-mount Customizable User Interface Terminal (2.8" TFT LCD with Touch Screen) that provides interaction between the User and the User’s Building Management System (BMS).   The device is configurable to display various N2 (or MS/TP) data and/or allow the user to modify this data. Further, the S2UI28 contains the following on-board peripherals which can be mapped backed into the BMS:

 a. Occupancy (PIR) Sensor
 b. Ambient Light Level Sensor (Reads in Lux and Foot-Candles)
 c. On-board Temperature Sensor
 d. Off-board JCI Compatible Platinum 1K Temperature Sensor
 for direct connection to external Controllers (VAVs, etc) 
 e. Two (2) 12- 24 AC/DC compatible Binary Inputs 

Johnson Control Users (N2 Bus HMI, N2 Bus Display) 

The S2UI28 has direct support for JCI's N2 bus as both a Slave and as a N2 Bus Master (Supervisory Controller).  As a N2 Slave the S2UI28 allows the Supervisory Controller to read and write to the S2UI28 to display various BMS information.  As a N2 Master (a mini Supervisory Controller), the S2UI28 can be connected to a small N2 network to display and modify various N2 field device data points (AI, AO, BI, BO, etc).

Specifications

Part Number:

  S2UI28-N2S     (N2 Slave Version)  (Available Now) 

  S2UI28-N2M    (N2 Master Version)  (Available Q2/2011) 

  S2UI28-MSTP   (BACNet MS/TP Version)   (Available Q2/2011)

 

Power Requirements:

    18-24 V AC/DC @ 300 mA (Max)

 

Environment: 

  Temperature -40 C to +60 C 

  Humidity: 10 - 95 % RH (non-condensing)

 

Dimensions:  

  3.56" W x 5.75"H x 1.2” H 

  9.04cm W x 14.60cm H x 3.05cm H

 

Weight:  

  6.5 oz

  187 grams

 

Display:

  2.8" TFT LCD 240x320,

   - LED Backlit with 262K Colors   

   - IntegratedTouch Screen 

 

On-Board Sensors:

  One (1) Ambient Light Level Sensor

    Range 0 to 3000 Lux or 0 to 280 Foot-Candles 

  One (1) Occupancy Sensor

  Two (2) Binary Inputs (12-24 AC/DC Compatible)

  One (1) Platinum RTD 1K ohm for direct connect to external controller 

  One (1) Temperature sensor (+/- 1 deg accuracy) read as a AI 

 

Data Interfaces:

  One (1) 3-Pin Electrically isolated RS-485 Interface

  One (1) USB Mini-B

  One (1) 10/100 Ethernet

 

Supported Protocols:

  JCI N2 Open (Slave and Master)

  BACNet MS/TP

  HTTP 


S2UI28 Technical Information: